Page 36 - 4587
P. 36

and earth.
           2.  If  the  neutral  is  not  accessible,  the  overvoltage  limiter  is
           installed between a phase and earth.
           3.  It  runs  off  external  over  voltages,  transmitted  by  the
           transformer, to the earth and protects the low voltage network from
           a  voltage  increase  due  to  flashover  between  the  transformer’s
           medium voltage and low voltage windings.

                                     Advantages

           1. System provides the best service continuity during use.
           2. When an insulation fault occurs, the short-circuit current is very
           low.
           3. Higher operational safety only a capacitive current flows, which
           is  caused  by  the  system  leakage  capacitance  if  an  earth  fault
           occurs.
           4.  Better  accident  prevention  the  fault  current  is  limited  by  the
           body impedance, earthing resistance and the high impedance of the
           earth fault loop.

                                    Disadvantages
           1.  Requires  presence  of  maintenance  personnel  to  monitor  and
           locate the first fault during use.
           2.  Requires  a  good  level  of  network  insulation  (High  leakage
           current must be supplied by insulating transformers).
           3. Overvoltage limiters must be installed.
           4.  Requires  all  the  installation’s  exposed  conductive  parts  to  be
           Same Voltage level. If this is not possible RCDs (residual-current
           device) must be installed.
           5. Locating faults is difficult in widespread networks.
           6. When an insulation fault with reference to the earth occurs, the
           voltage of the two healthy phases in relation to the earth take on
           the  value  of  the  phase-to-phase  voltage  So  when  Select  Size  of
           equipments it is need to higher insulation level of the Equipments.
           7.  The  risk  of  high  internal  over  voltages  makes  it  advisable  to
           reinforce the equipment insulation.
           8. The compulsory insulation monitoring, with visual and audible
           indication  of  the  first  fault  if  tripping  is  not  triggered  until  the
           second fault occurs.
           9. Protection against direct and indirect contact is not guaranteed.

                                          35
   31   32   33   34   35   36   37   38   39   40   41