Page 38 - 4587
P. 38

7.  Special  measures  must  be  taken  for  the  loads  or  parts  of  the
           installation causing high leakage currents during normal operation
           in  order  to  avoid  spurious  tripping  (feed  the  loads  by  insulating
           transformers  or  use  high  threshold  RCDs,  compatible  with  the
           exposed conductive part earth resistance).
           8.  Very  high  fault  currents  leading  to  maximum  damage  and
           disturbance in telecommunication networks.
           9. The  risk for personnel  is  high while the fault lasts; the touch
           voltages which develop being high.
           10. Requires the use of differential protection devices so that the
           fault clearance time is not long. These systems are costly.

           (2) TN System: Neutral-connected exposed conductive part
           • First letter T = the neutral is directly earthed at Transformer.
           • Second letter N = the Frames of Electrical loads are connected to
           the neutral Conductor.
           There  are  two  types  of  TN  systems,  depending  on  whether  the
           neutral conductor and Earth conductor are combined or not:
                                      (2a) TN-C
           • In TNC System (the third letter C = combined neutral and earth
           conductor),  the  neutral  and  earth  conductors  are  combined  in  a
           single conductor and earthed at source end.
           • This combined neutral-earth wire is than distributed to load side.
           • In this system earthing connections must be evenly placed along
           the length of the neutral-(earth) conductor to avoid potential rises
           in the exposed conductive parts at Load Side if a fault occurs.
           • This system must not be used for copper cross-sections of less
           than 10 mm² and aluminum cross-sections of less than 16 mm², as
           well as downstream of a TNS system (As per IEC 60364-5).

                                System Characteristics
           1. Low earth fault loop impedance.
           2. High earth fault current.
           3. More than one earth fault loops.
                                     Advantages
           1. No earth wire required; allow multi-point earth.
           2. Better earthing continuity.
           3. Neutral never have float voltage.
           4.  Impedance of earth fault loop could be predicted.
           5.  The  TNC  system  may  be  less  costly  upon  installation

                                          37
   33   34   35   36   37   38   39   40   41   42   43