deformation of the nozzles, incomplete combustion of fuel and
            its over-consumption, and reduction of engine power.
                   Therefore,  diesel  fuel  regulates  both  maximum  and
            minimum  viscosity.  So,  for  summer  fuel,  the  kinematic
            viscosity must be within range 3,0...6,0 сSt, winter – 1,8...6,0
            сSt  (according  to  National  Standards  of  Ukraine  3868-99)  і
                                               0
            2,0…4,5    сSt  at  temperature  40  С  (according  to  National
            Standards of Ukraine 4840-2007).
                   Kinematic  viscosity  of  petroleum  products  is
            determined by GOST 33-66.
                   Vizkosimeter is a U-shaped tube (Figure 9.1) with three
            extensions,  in  a  narrow  circle  2  of  which  a  capillary  5  is
            lengthened in length of 0,075 m. Vazkosimetri are made with
                                                                     -3
            different  diameters  of  the  capillary:  from  (0,4  tо  40)10   m.
            Above the capillary there are two extensions 4 and 3. The lower
            extension 6 serves as a reservoir where the liquid flows when
            determining the  viscosity. The expansion  is  made  in order to
            keep  the  height  of  the  column  of  liquid  under  the  action  of
            leakage constant. The upper part of the wide lap 1 has a nozzle
            for attaching a rubber tube 7 to a pear. On the upper extensions,
            the  viscosimeter  number,  its  nominal  diameter  is  affixed.  By
            number  and  diameter  of  the  capillary,  a  stable  viscometer  is
            found in the factory passport.
                   To  maintain  a  constant  temperature,  the  dosimeter  is
            immersed  in  a  liquid  thermostat.  Thermometer  9  of  the
            thermostat  must  have  a  price  point  0,1  С.  To  fill  the
            thermostat, use distilled water.
                   The diameters of the capillary viscometer are chosen in
            such a way that the time of leakage of the explored fuel it was
            within 60...120 s.
                   On the side of the viscometer, put a rubber tube with a
            pear, turn the viscometer on 180 С and immerse a narrow knee
            in a glass with the fuel being studied (Fig. 9.1 b). Having closed