-    All  socket-outlet  circuits  rated  not  more  than  32  A  for
           construction sites (where reduced low voltage, etc. is not used).
             -    All  socket  outlets  supplying equipment  outside mobile or
           transportable units.
             -    All circuits in caravans.
             -    All circuits in circuses, etc.
             -    A  circuit  supplying  Class  II  heating  equipment  for  floor
           and ceiling heating systems


             100 mA
                  Applications
             -    Socket  outlets  of  rating  exceeding  32  A  in  agricultural
           locations.
             -    Where Loop Impedances are too high, RCD ratings can be
           calculated.


             300 mA
                  Applications
             -    At the origin of a temporary supply to circuses, etc.
             -    Where there is a risk of fire due to storage of combustible
           materials.
             -    All circuits (except socket outlets) in agricultural locations


             500 mA
                  Applications
             -    Any circuit supplying one or more socket outlets of rating
           exceeding 32 A, on a construction site

           3     Make a written translation of the following:

             The  regulations  recommend,  therefore,  that  the  preferred
           method of earth fault protection for installations in TT systems be
           achieved by RCDs, such that the product of its residual operating
           current and the loop impedance will not exceed a figure of 50 V.
             Residual  current  breakers  (RCBs),  residual  current  circuit
           breakers (RCCBs) and RCDs are one and the same thing.
             Modern  developments  in  CB  (circuit  breaker),  RCD  and