Figure 2.2 - Flexible steel conduits for electrical cables

             For most substation applications, there will be more than two
           conductors in a conduit, so the maximum fill percentage will be
           40%.
             It is important to consider the length of the conduit run and the
           number of bends in the conduit runs when determining the amount
           of  fill  that  is  acceptable.  The  maximum  fill  percentage  will  not
           guarantee  an  easy  installation.  Other  considerations  associated
           with  the  fill  of  the  conduit  and  the  ease  of  installation  is  the
           jamming  ratio.  While  the  NEC  does  not  govern  this,  it  does
           contain an informational note about its occurrence.
             There are many different requirements for ampacity de-rating of
           cables.





                                          13